Flexural strength of reinforced foam concrete for industrial roof
Loading...
Date
item.page.authors
Journal Title
Journal ISSN
Volume Title
Publisher
Abstract
An attempt is made in this thesis to find out if the foam concrete can be used for industrial roofing purpose where load carrying requirement is less. Densities of foam concrete ranging from 1200 kg/m3 to 1600 kg/m3 was prepared with the cement to sand mix ratio of 1:1
newlineand subjected to compressive test, split tensile test, flexural test and water absorption tests. Also
newlinefoam concrete mix of density 1600 kg/m3 was prepared with the cement to sand mix ratio of
newline1:1.5 and 1:2 and subjected to compressive test, split tensile test, flexural test and water absorption tests. The test results were compared to the test results of the normal mix without foam. It was noticed that as the density of the foam concrete increased, the strength also
newlineincreased and the percentage of water absorption reduced. It was also noticed that as the percentage of fine aggregate in foam concrete increased with constant density, the strength decreased and the percentage of water absorption increased. By plotting the trend curve it was
newlinenoticed that the twenty-eighth-day split tensile strength, flexural strength and percentage of
newlinewater absorption of 1:1 ratio of foam concrete with density of 1500 kg/m3 and higher will yield
newlinemore or less equal or better results than 1:2 and higher cement to sand mix ratio of normal mix mortar. This indicated that the foam concrete of density 1500 kg/m3 and higher with cement to sand mix ratio of 1:1 can be considered to be used in places where normal cement mortar mix of
newline1:2 and higher are being used for structural purposes.
newlineEight types of foam concrete slabs with different reinforcements and thickness was subjected to flexural test and verified if it can be used for industrial roof from flexural strength
newlinepoint of view. The test results obtained were compared with the test results of normal mix slabs
newlinewithout foam of same mix proportion, types of reinforcement and thickness. The test results
newlineshowed that, as the percentage of reinforcement and thickness of foam concrete slab specimen increased