Performance Analysis of Earth Air Pipe Heat Exchanger as Passive Cooling and Heating System
Loading...
Date
item.page.authors
Journal Title
Journal ISSN
Volume Title
Publisher
Abstract
The working principle of EAPHE, as passive heating and cooling system, is based upon the
newlineutilization of soil as source and sink of heat for winter heating and summer cooling respectively.
newlineEAPHE consists of long pipes laid under the ground having one end open in air and the other
newlineconnected to the air intake of buildings. Hot or cold outdoor air is passed through the buried
newlinepipes for bringing change in its temperature before supplying it into the building. A turbulent
newlinemodel has been developed based on Computational Fluid Dynamics (CFD) to predict the
newlineperformance of EAPHE system. Model was simulated in ANSYS FLUENT and performance
newlineof proposed models has been investigated, and comparisons were made in terms of outlet air
newlinetemperature, sub-soil temperature at 0.05m and 0.25m from pipe surface, heat transfer rate,
newlinecoefficient of performance (COP) and effectiveness of the system. The developed model has
newlinebeen validated against the numerical and experimental results of published research papers.
newlineCommon configuration of EAPHE system usually consider straight or U shaped geometrical
newlinelayout, which requires a large installation area which is not suitable for installation under small
newlinehome or office setup in a densely populated country like India. In present study this major
newlinedrawback can be overcome by using helical shaped air pipe layout, which reduces the
newlineinstallation area up to 77% compared to that of the conventional straight or U shaped pipe
newlinegeometry. Installation area of the helical air pipe layout depending upon pitch of the helical
newlinepipe and coil diameter.