Certain improvements in source current harmonics reduction for an induction motor with shunt active filter
Loading...
Date
item.page.authors
Journal Title
Journal ISSN
Volume Title
Publisher
Abstract
The recent developments in the power electronic fields have
newlineattracted more applications of non-linear loads such as adjustable speed
newlinedrives, traction drives, UPS, battery chargers, etc. These loads have inherently
newlineintroduced the harmonics in the tied power system and cause many power
newlinequality issues like electromagnetic interferences (EMI), malfunctioning of
newlinerelays and circuit breakers, de-rating of power devices, heating losses and their
newlineassociated problems. The harmonics are to be eliminated or reduced by using
newlinepower filters with proper control techniques. In many research articles, the
newlineknown method of shunt active filters being introduced in the PCC and load
newlineend has been reported. This research work has demonstrated the performance
newlineenhancement of VSI fed induction motor by introducing a new scheme of
newlineShunt Active Filter (SAF) at the supply end. The SAF performs the reduction
newlineof source current harmonics due to non-linear load like VSI fed three phase
newlineinduction motor. The instantaneous active and reactive current control
newlinetechniques have been implemented and studied using different controllers.
newlineShunt active filter has been used to generate the equal but opposite harmonic
newlinecurrents to cancel the effects of harmonic currents drawn by the non-linear
newlineload from the supply. The proposed system has been studied with PI, PID,
newlineFuzzy logic, ANN and Fractional order PID controllers. The main goal of this
newlineresearch work is to enhance the power quality by the way of reducing the
newlinesupply current harmonic THDs. The proposed research work has been
newlinesimulated using MATLAB software and its simulation results have been
newlineverified by the experimental results. The results have indicated a low source
newlinecurrent harmonic THD of 2.72% owing to the introduction of the shunt active
newlinefilter on the supply side and closed loop control.