Dynamicmodelingand control strategies of upqcfor simultaneous voltage andcurrent compensation
Loading...
Date
item.page.authors
Journal Title
Journal ISSN
Volume Title
Publisher
Abstract
Today utility network still significantly suffers from some low
newlinepower quality factors. The poor reliability and quality of power supply may
newlinecause many complex and serious problems. And high quality of power has
newlinebeen more and more required by increasing number of sensitive loads.
newlineHarmonics generated by nonlinear loads, voltage sag, and high frequency
newlinecomponents caused by switched capacitors are some known sources seriously
newlinedegrading the quality of supply in the power network. Power system can employ many attractive applications of power
newlineelectronics technologies for power quality improvement. Voltage-source
newlineconverter based custom power devices are increasingly being used in custom
newlinepower applications to mitigate power quality problems in power distribution
newlinesystems. One modern and very promising solution is the unified power quality
newlineconditioner.
newlineUnified Power Quality Conditioner(UPQC) is a custom power
newlinedevice that consists of shunt and series converters connected back to back on
newlinethe dc side and deals with load current and supply voltage imperfections. It
newlinecan compensate for power quality problems such as voltage harmonics,
newlinevoltage unbalance, voltage flickers, voltage sags, voltage swells, current
newlineharmonics, current unbalance, reactive current, etc. The active power filtering
newlinehas proven to be one of the best solutions for mitigation of major power quality problems. The operation of UPQC isolates the utility from current
newlinequality problems of load and in the same time, isolates the load from voltage
newlinequality problems of utility. The shunt active filter is utilized to overcome all current related
newlineproblems, such as current harmonics, reactive current and current unbalance.
newlineWhereas, all voltage related problems, such as voltage harmonics, voltage sag
newlineand swell, and voltage unbalance, are handled by using the series active filter. The UPQC is controlled in such a way that the voltage at load bus is always
newlinesinusoidal and has a desired magnitude.
newline